XLP/PVC Instrumentation Cable - Shielded Multi Conductor

600 Volts, 90°C Wet or Dry
DESCRIPTION:
| Conductor: | Bare, annealed copper per ASTM B33. Class B stranding per ASTM B8. |
| Sizes: | #18 AWG – #16 AWG |
| Insulation: | Extruded flame-retardant cross-linked polyolefin (XLP). |
| Cable: | Conductors cabled together with fillers as needed to form a round core. An overall aluminum mylar shield and drain wire is applied over the core. |
| Color Code: | E1 Per ICEA S-73-532 Table E1 (Old K1) E2 Per ICEA S-73-532 Table E2 (Old K2) (See Technical section for color code tables) |
| Jacket: | Flame-retardant, sunlight resistant, ER rated, Polyvinyl Chloride (PVC). |
| Options: | Available with class K stranding per ASTM B174. Available with class H stranding per ASTM B173. Available with tinned copper conductors. |
Applications / Installation:
For use as a 600 volt, multi conductor instrumentation cable where flame retardance, and
moisture/chemical resistance is critical. Cable can be installed in free air, in raceways or direct
burial. The cable is also approved for wet or dry locations as well as Class 1 Division II industrial
hazardous locations per NEC 501-4(b) for (UL) Type tray cables (TC).
Features and Benefits:
Temperature rating of 90°C wet or dry. Insulation provides excellent electrical, thermal, and physical properties, excellent flame resistance and resistant to crush, compression, cuts and
heat deformation. Also conductor insulation provides good low temperature (-25°C) cold bend characteristics.Approvals:
Insulated Conductor: – VW-1Cable: – Direct Burial, sunlight resistant, ER rated
UL Type TC, 90°C Wet or Dry, 600V
Passes UL 1277 Flame Test (70,000 BTU/hr)
Passes IEEE 383 Flame Test (70,000 BTU/hr)
ICEA S-66-524, 90°C Wet or Dry, 600V & 1000V
Passes IEEE 1202 Flame Test (70,000 BTU/hr)
Passes ICEA T-29-520 Flame Test (210,000 BTU/hr)
XLP/PVC Instrumentation Cable - Shielded Multi Conductor
| AWG | Number of Conductors | Insulation Thickness | Jacket Thickness | Overall Diameter | Weight lbs/1000 ft |
| 18 | 2 | 0.025 | 0.045 | .300 | 50 |
| 18 | 3 | 0.025 | 0.045 | .310 | 55 |
| 18 | 4 | 0.025 | 0.045 | .335 | 65 |
| 18 | 5 | 0.025 | 0.045 | .370 | 75 |
| 18 | 6 | 0.025 | 0.045 | .395 | 90 |
| 18 | 7 | 0.025 | 0.045 | .405 | 95 |
| 18 | 9 | 0.025 | 0.045 | .440 | 110 |
| 18 | 12 | 0.025 | 0.045 | .500 | 140 |
| 18 | 15 | 0.025 | 0.060 | .590 | 190 |
| 18 | 19 | 0.025 | 0.060 | .625 | 230 |
| 16 | 2 | 0.025 | 0.045 | .325 | 60 |
| 16 | 3 | 0.025 | 0.045 | .340 | 70 |
| 16 | 4 | 0.025 | 0.045 | .370 | 80 |
| 16 | 5 | 0.025 | 0.045 | .400 | 95 |
| 16 | 6 | 0.025 | 0.045 | .425 | 110 |
| 16 | 7 | 0.025 | 0.045 | .435 | 125 |
| 16 | 9 | 0.025 | 0.045 | .500 | 155 |
| 16 | 12 | 0.025 | 0.060 | .600 | 210 |
| 16 | 15 | 0.025 | 0.060 | .660 | 260 |
| 16 | 19 | 0.025 | 0.060 | .700 | 310 |