XLP/PVC Instrumentation Cable - Shielded Triads

600 Volts, 90°C Wet or Dry
DESCRIPTION:
| Conductor: | Bare, annealed copper per ASTM B33. Class B stranding per ASTM B8. |
| Sizes: | #18 AWG – #16 AWG |
| Insulation: | Extruded flame-retardant cross-linked polyolefin (XLP). |
| Triad: | Three conductors twisted together with a drain wire and aluminum mylar shield. |
| Cable: | Shielded triads cabled together with fillers as needed to form a round core. An overall aluminum mylar shield and drain wire is applied over the core. |
| Color Code: | Triads are black, white and red with the triad number printed on the white conductor. |
| Jacket: | Flame-retardant, sunlight resistant, ER rated, Polyvinyl Chloride (PVC). |
| Options: | Available with class K stranding per ASTM B174. Available with class H stranding per ASTM B173. Available with tinned copper conductors. |
Applications / Installation:
For use as a 600 volt, multi triad instrumentation cable where flame retardance, and
moisture/chemical resistance is critical. Cable can be installed in free air, in raceways or
direct burial. The cable is also approved for wet or dry locations as well as Class 1 Division II
industrial hazardous locations per NEC 501-4(b) for (UL) Type tray cables (TC).
Features and Benefits:
Temperature rating of 90°C wet or dry. Insulation provides excellent electrical, thermal, and physical properties, excellent flame resistance and resistant to crush, compression, cuts and heat
deformation. Also conductor insulation provides good low temperature (-25°C) cold bend characteristics.Approvals:
Insulated Conductor: – VW-1Cable: – Direct Burial, sunlight resistant, ER rated
UL Type TC, 90°C Wet or Dry, 600V
Passes UL 1277 Flame Test (70,000 BTU/hr)
Passes IEEE 383 Flame Test (70,000 BTU/hr)
ICEA S-66-524, 90°C Wet or Dry, 600V & 1000V
Passes IEEE 1202 Flame Test (70,000 BTU/hr)
Passes ICEA T-29-520 Flame Test (210,000 BTU/hr)
XLP/PVC Instrumentation Cable - Shielded Triads
| AWG | Number of Shielded Triads | Insulation Thickness | Jacket Thickness | Overall Diameter | Weight lbs/1000 ft |
| 18 | 1 | 0.025 | 0.045 | 0.310 | 55 |
| 18 | 2 | 0.025 | 0.060 | 0.560 | 140 |
| 18 | 3 | 0.025 | 0.060 | 0.590 | 170 |
| 18 | 4 | 0.025 | 0.060 | 0.645 | 210 |
| 18 | 6 | 0.025 | 0.060 | 0.730 | 295 |
| 18 | 8 | 0.025 | 0.060 | 0.860 | 395 |
| 18 | 10 | 0.025 | 0.080 | 0.945 | 470 |
| 18 | 12 | 0.025 | 0.080 | 1.015 | 535 |
| 18 | 16 | 0.025 | 0.080 | 1.145 | 690 |
| 18 | 24 | 0.025 | 0.080 | 1.365 | 1005 |
| 16 | 1 | 0.025 | 0.045 | 0.340 | 70 |
| 16 | 2 | 0.025 | 0.060 | 0.620 | 160 |
| 16 | 3 | 0.025 | 0.060 | 0.655 | 210 |
| 16 | 4 | 0.025 | 0.060 | 0.720 | 260 |
| 16 | 6 | 0.025 | 0.060 | 0.815 | 365 |
| 16 | 8 | 0.025 | 0.060 | 0.960 | 500 |
| 16 | 10 | 0.025 | 0.080 | 1.055 | 600 |
| 16 | 12 | 0.025 | 0.080 | 1.135 | 705 |
| 16 | 16 | 0.025 | 0.080 | 1.285 | 890 |
| 16 | 24 | 0.025 | 0.080 | 1.540 | 1310 |
Dimensions and weights shown are nominal, subject to industry tolerances. Dimensions and weights for other cable configurations are available upon request.