XLP/CPE Thermocouple Cable


INDUSTRIAL TRAY CABLE
600 Volts, 90°C Wet or Dry
DESCRIPTION:
   
Conductor:Thermocouple alloy per ANSI MC 96.1 – 1982.
Sizes:#20 AWG – #16 AWG
Insulation:Extruded flame-retardant cross-linked polyolefin (XLP).
Pair:Conductors twisted together with a drain wire and aluminum mylar shield.
Cable:Shielded pairs cabled together with fillers as needed to form a round core. An overall aluminum mylar shield and drain wire is applied over the core.
Color Code:Pairs are color coded per thermocouple type with pair number printed on the negative (red) conductor. See chart on back for specific color codes.
Jacket:Black, flame-retardant, sunlight resistant, ER rated
Chlorinated Polyethylene (CPE).
Options:Available with class B stranding per ASTM B174.
Available with color coded jacket.

Applications / Installation:
For use as a 600 volt, multi pair thermocouple instrumentation cable where flame-retardance, and moisture/chemical resistance is critical. Cable can be installed in free air, in raceways or direct burial. The cable is also approved for wet or dry locations as well as Class 1 Division II industrial hazardous locations per NEC 501-4(b) for (UL) Type tray cables (TC).


Features and Benefits:
Temperature rating of 90°C wet or dry. Insulation provides excellent electrical, thermal, and physical properties, excellent flame resistance and resistant to crush, compression, cuts and heat deformation. Also conductor insulation provides good low temperature (-40°C) cold bend characteristics.


Approvals:
Insulated Conductor: – VW-1
Cable: – Direct Burial, sunlight resistant, ER rated
UL Type TC, 90°C Wet or Dry, 600V
Passes UL 1277 Flame Test (70,000 BTU/hr)
Passes IEEE 383 Flame Test (70,000 BTU/hr)
ICEA S-82-552, 90°C Wet or Dry, 600V
Passes IEEE 1202 Flame Test (70,000 BTU/hr)
Passes ICEA T-29-520 Flame Test (210,000 BTU/hr)


XLP/CPE Thermocouple Cable

AWGNumber of
Shielded Pairs
Insulation
Thickness
Jacket
Thickness
Overall
Diameter
Weight
lbs/1000 ft
2010.0250.0450.27035
2020.0250.0450.43070
2030.0250.0450.45085
2040.0250.0450.500105
2060.0250.0600.600160
2080.0250.0600.670210
20100.0250.0600.735240
20120.0250.0600.790280
20160.0250.0800.890360
20240.0250.0801.060500
1810.0250.0450.30050
1820.0250.0450.48090
1830.0250.0450.510115
1840.025 0.0600.595165
1860.025 0.0600.670220
1880.025 0.0600.750280
18100.025 0.0600.820340
18120.0250.0800.930430
18160.0250.0801.045540
18240.0250.0801.235760
1610.0250.0450.32560
1620.0250.0450.570130
1630.0250.0600.600160
1640.0250.0600.660200
1660.0250.0600.740270
1680.0250.0600.880380
16100.0250.0800.970460
16120.0250.0801.035530
16160.0250.0801.165570
16240.0250.0801.400960


Dimensions and weights shown are nominal, subject to industry tolerances. Dimensions and weights for other cable configurations are available upon request.

EX – Color CodeChromel (Positive)
Constantan (Negative)
PURPLE
RED
JX – Color CodeIron (Positive)
Constantan (Negative)
WHITE
RED
TX – Color CodeCopper (Positive)
Constantan (Negative)

BLUE
RED

KX – Color CodeChromel (Positive)
Alumel (Negative)
YELLOW
RED